Reports until 15:56, Tuesday 19 November 2013
H1 SUS
arnaud.pele@LIGO.ORG - posted 15:56, Tuesday 19 November 2013 (8628)
sus filter files modified

After the recent sus model changes (ECR E1300578), and since some channels have been deleted, we were seeing in foton the kind of errors described below, when opening a filter file  :

line 500: Unknown filter module PR2_M1_OFFLOAD_RX line 501: Illegal filter section: -1.1136890503818733 0.6048077715301807 2.0000000033150198 1.0000000033159222
line 497: Design for unknown filter module PR2_M1_OFFLOAD_RX

In order to fix it, and from Jim B's suggestion, every text file containing an error have been opened and saved under foton (apparently, foton would automatically delete the non existing channels and filters from the textfile).

This has been done for : ITMX ITMY ETMY MC1 MC2 MC3 SRM SR2 SR3 PRM PR2 PR3

Attached are the logs of what have been done so far :

1) svn_diff shows the change between the filterfile on the svn (saved before model changes) and the filterfile after the model changes

2) diff_old_new shows the change between the filterfile before and after resaving it with foton

The new filterfiles have been commited under revision 6437 of the svn

Non-image files attached to this report