TITLE: 02/05 Day Shift: 16:00-00:00 UTC (08:00-16:00 PST), all times posted in UTC
STATE of H1: Commissioning
INCOMING OPERATOR: None
SHIFT SUMMARY:
16:00 (8:00) Start of shift
16:20 (8:20) Richard to LVEA -- HAM6 work
16:39 (8:39) Chris, pest control to LVEA
16:46 (8:46) TJ to Optics Lab, LVEA -- Hartmann work
16:47 (8:47) Danny to LVEA -- SRM work
16:48 (8:48) Tvo to LVEA -- CO2Y work
16:52 (8:52) Chris out of LVEA, going to EX, EY
17:14 (9:14) Patrick to HAM6 -- record numbers on cables
17:39 (9:39) Gerardo to MY -- assist Kyle
17:39 (9:39) Karen to LVEA
17:44 (9:44) Patrick out of LVEA
17:47 (9:47) Jamie beginning Guardian restart
18:09 (10:09) Marie to LVEA -- TCS work
18:15 (10:15) Dick to LVEA -- RF work
18:23 (10:23) Robert to LVEA
18:25 (10:25) Rich, Dean to HAM6
18:28 (10:28) Marc to LVEA -- assist Dick
19:20 (11:20) Tvo, TJ out of LVEA
19:24 (11:24) Karen out of LVEA
19:41 (11:41) Rich, Dean to HAM6
19:54 (11:54) Kyle back from MY
19:55 (11:55) Robert to EX
20:08 (12:08) Kyle to LVEA -- Look at flange thickness
20:13 (12:13) Kyle out of LVEA
20:30 (12:30) Rich, Dean out of LVEA
20:35 (12:35) Kyle to LVEA
20:36 (12:36) Jim to EX -- realign BRS
20:50 (12:50) Chris to EX, EY -- fan room work
21:02 (13:02) Marc, Dick out of LVEA
21:12 (13:12) Nutsinee Optics Lab
21:14 (13:14) Rich, Dean to LVEA
21:49 (13:49) Robert, Kara back from EX
21:52 (13:52) Chris leaving EX, EY
23:09 (15:09) Kyle to MY
23:34 (15:34) Peter to Optics Lab
00:00 (16:00) End of shift
2019-02-05 15:11:00.366551
There are 6 T240 proof masses out of range ( > 0.3 [V] )!
ETMX T240 1 DOF X/U = 0.36 [V]
ETMX T240 1 DOF Z/W = 0.341 [V]
ETMX T240 2 DOF Y/V = -0.617 [V]
ITMX T240 1 DOF X/U = -0.365 [V]
ITMX T240 3 DOF X/U = -0.306 [V]
ITMY T240 3 DOF Z/W = -0.478 [V]
All other proof masses are within range ( < 0.3 [V] ):
ETMX T240 1 DOF Y/V = 0.292 [V]
ETMX T240 2 DOF X/U = -0.24 [V]
ETMX T240 2 DOF Z/W = 0.197 [V]
ETMX T240 3 DOF X/U = 0.28 [V]
ETMX T240 3 DOF Y/V = 0.228 [V]
ETMX T240 3 DOF Z/W = 0.264 [V]
ETMY T240 1 DOF X/U = -0.021 [V]
ETMY T240 1 DOF Y/V = 0.281 [V]
ETMY T240 1 DOF Z/W = -0.009 [V]
ETMY T240 2 DOF X/U = 0.027 [V]
ETMY T240 2 DOF Y/V = -0.056 [V]
ETMY T240 2 DOF Z/W = -0.011 [V]
ETMY T240 3 DOF X/U = -0.015 [V]
ETMY T240 3 DOF Y/V = -0.012 [V]
ETMY T240 3 DOF Z/W = 0.183 [V]
ITMX T240 1 DOF Y/V = 0.126 [V]
ITMX T240 1 DOF Z/W = 0.116 [V]
ITMX T240 2 DOF X/U = 0.151 [V]
ITMX T240 2 DOF Y/V = 0.139 [V]
ITMX T240 2 DOF Z/W = 0.233 [V]
ITMX T240 3 DOF Y/V = 0.134 [V]
ITMX T240 3 DOF Z/W = 0.035 [V]
ITMY T240 1 DOF X/U = 0.199 [V]
ITMY T240 1 DOF Y/V = 0.13 [V]
ITMY T240 1 DOF Z/W = 0.156 [V]
ITMY T240 2 DOF X/U = 0.161 [V]
ITMY T240 2 DOF Y/V = 0.242 [V]
ITMY T240 2 DOF Z/W = 0.211 [V]
ITMY T240 3 DOF X/U = -0.096 [V]
ITMY T240 3 DOF Y/V = 0.211 [V]
2019-02-05 15:10:58.358910
There are 1 STS proof masses out of range ( > 2.0 [V] )!
STS A DOF X/U = -7.991 [V]
All other proof masses are within range ( < 2.0 [V] ):
STS A DOF Y/V = -0.838 [V]
STS A DOF Z/W = -0.324 [V]
STS B DOF X/U = 0.317 [V]
STS B DOF Y/V = 0.38 [V]
STS B DOF Z/W = -0.393 [V]
STS C DOF X/U = 0.326 [V]
STS C DOF Y/V = 0.237 [V]
STS C DOF Z/W = 0.613 [V]
STS EX DOF X/U = -0.107 [V]
STS EX DOF Y/V = 0.278 [V]
STS EX DOF Z/W = 0.214 [V]
STS EY DOF X/U = 0.302 [V]
STS EY DOF Y/V = -0.12 [V]
STS EY DOF Z/W = 0.707 [V]
Gerardo M., Kyle R.
Today, we removed the actuator covers from GV9 and GV10 so as to verify the presence of a spindle nut (retaining nut?), anti-rotation washer (spindle nut lock washer?) and to record the ball/detent torque pre-load as indicated on the graduated scale. In both cases, the nuts and washers were present but neither appeared to have a tab if the washer bent so as to engage with the key slot on the shaft or nut. This has been the case for all valves inspected up to this point. My understanding is that this nut and washer don't appear in the GNB drawings and may have been added during installation(?). Without documentation, we aren't 100% sure as to what was intended but, typically with the arrangement, one tab of the washer would be bent to engage with shaft's keyed slot and a different tab would be bent to engage with the nut so as to prevent the nut from rotating independent of the shaft.
I didn't have my camera with me at the time but both GV9 and GV10's "pointer" capscrews were aligned with the "4" position. Three thread crests were showing above the nut.
I noticed yesterday that Seismon was not recovered after the file system issues yesterday, but I caught it after Carlos had left for the day, so I didn't get to ask if they were still recovering. Working with Carlos this morning I was able to get it back up and running, but I wanted to capture the process here.
1. ssh onto the seismon vm as controls:
ssh controls@seismon
2. Launch 2 screen sessions for the seismon scripts, this is not completely straight forward. The scripts live in /usr/local/seismon/seismon/bin, but 2 of them need a virtual environment, which I launched using an alias:
controls@seismon:~ 0$ cd /usr/local/seismon/seismon/bin
controls@seismon:bin 0$ screen
Activate the virtual environment for seismon:
controls@seismon:bin 0$ seismon_ve
Then run the traveltimes script:
(ve) controls@seismon:bin 0$ ./seismon_run_traveltimes.py
This will start outputting stuff to the terminal, so leave it running and CTRL+A+D to disconnect from the screen session, launch a new screen session and repeat for seismon_run_info, including the seismon virtualenv (seismon_ve alias).
3. The run a third screen session for the epics client seismon_epics_client_v5.py. this does NOT use the seismon virtualenv, and won't run with it set. When done there should be 3 screen sessions running.
controls@seismon:bin 0$ screen
controls@seismon:bin 0$ ./seismon_epics_client_v5.py
4. There is also an epics IOC on h1fescript0, ssh to that machine as controls and ps -elf | grep seis to see there is only one copy of seismon_epics_ioc_v3.py running.
controls@h1fescript0:~ 0$ ps -elf |grep seis
0 S controls 2952 2590 1 80 0 - 32756 poll_s 2018 pts/2 18:20:36 python ./seismon_epics_ioc_v3.py
0 S controls 4532 4301 0 80 0 - 2350 pipe_w 14:21 pts/0 00:00:00 grep --color=auto seis
That should be it.
TJ, Marie, TVo, Danny
TJ set up a temporary rail for the table to slide along to avoid the table from changing angle of incidence on the first in-vaccum mirror when shifting the table position.
After shifting the table a bit more to the left of where we nominally were trying, we were able to pass the CO2 beam through the ifo beam position in yaw (using the procedure detailed in alog 46766). I forgot to take photos of the red alignment laser position on the Zn-Se viewport and SRM-HR baffle but I'll supplement this post with those photos as a comment next Tuesday.
There was quite a bit of pitch motion/drift on the AS_A_DC and AS_B_DC pds. Not very clear why this was, but the motion made it difficult to verify the pitch alignment was still good. We might have to double check next Tuesday (or sooner if there is a need to test) but I suspect that we are nominally in a good position in pitch since we made very little changes.
ODC removal
Keita, Jeff, Jamie, Dave:
The following models were restarted after ODC removal: h1sus{etm[x,y], tms[x,y], itm[x,y], bs, pr[m,2,3], sr[m,2,3], mc[1,2,3], omc, opo, im, htts} h1isietm[x,y], h1isce[x,y].
ISC model changes:
Jenne, Daniel, Dave:
The following models were restarted: h1ascimc, h1omc
Guardian new base code:
Jamie:
h1guardian1's guardian base was updated. Its OS was upgraded and the machine was rebooted. The EDCU to connect to the new channels.
h1odcmaster removal
Dave:
I completed the h1odcmaster model removal from the DAQ with a new H1EDCU_DAQ.ini.
DAQ Restart
Dave:
The DAQ was restarted at 11:44PST for the above changes.
After the CAL-CS model upgrade to have highpass/whitening filters on the CFTD CTRL paths, I've installed whitening filters on the CFTD paths. This is the same as we did at LLO (see LLO aLOG 42961). This has to be installed on both inverse sensing and actuation paths, but does not need to be in the CFTD_DELTAL_EXTERNAL whitening bank. We will dewhiten in DTT. These are installed in FM1 of the CFTD_DARM_ERR bank and FM1 for each of the CFTD_DELTAL_CTRL*_HP banks. The design string is: zpk([0.3;0.3;0.3;0.3;0.3;0.3],[30;30;30;30;30;30],1,"n")
Overnight the end station BRS enclosures at both endstations heated up about .5 degrees C. This very nearly drove BRSX out of range, which would have probably tripped the ISI. This wasn't a big issue for BRSY, but BRSX went through 8k counts of the ~28k usable range, it probably also has an effect on the noise of the BRS. The damping for the BRS also goes unstable when the ccd image goes out of range.
Attached plot shows trends for the last week of each BRS driftmon, X is the left image, Y is the right. The BRS go out of range at about +/- 15000 counts, BRSX will need adjusted immediately, unless temperatures are changing back.
Was there some change to building heating or something? Nothing was changed on either BRS enclosure.
All 4 quads also see movement over the same time period. Attached trends are the last week of the quad topstage osems.
The FMCS controlled set point was not changed at either end station.
We've seen a similar issue before with the ETM temperature. It stems from the fact that the HVAC is stabilizing the average temperature of 4 temperature sensors: (A+B+C+D)/4.
The ETM chamber is down at one end of the building (near A & B). If, for example, the local temperature rises at the other end of the building (near temperature sensors C&D) then the HVAC reacts to keep the average temperature constant. A little bit of math shows that if C+D becomes hotter than A+B must become cooler. (Or it could be that the region near A is getting cooler and forcing C+D to get hotter - which is probably more likely given the current weather).
You can see that the ETM BRS DRIFTMON is much more strongly correlated with individual temperature sensors than with the average temperature. Stabilizing the VEA temperature to (A+B)/2 should minimize this issue.

Here's similar data from the LLO ETM - the RH RTD is much more strongly correlated with the 202B temperature sensor than it is with the average temperature.

I've done a quick rebalance of BRSX to get it closer to the middle of it's range, it's still damping down and temperatures will take a little while to stabilize. We may want to think about some weekly-ish checks of things that can get driven by temperature swings? I don't know what that would look like.
J. Kissel 8077 Reconciling SDFs prior to the h1iscex/h1iscey model restarts, I've accepted QPD offsets that were last changed on Jan 27th 2019. see attached screenshots.
Some of h1susetmx and h1susetmy L2 GAINs and associated TRAMPs were accepted.
Channel new (old)
H1:SUS-ETMX_L2_DRIVEALIGN_P2L_GAIN 2.647711781 (2.655)
H1:SUS-ETMX_L2_DRIVEALIGN_Y2L_GAIN 3.2292331724 (2.7)
H1:SUS-ETMX_L2_LOCK_P_GAIN 1.05 (1.04)
H1:SUS-ETMX_L2_LOCK_Y_GAIN 1.0 (0.99)
H1:SUS-ETMY_L2_DRIVEALIGN_P2L_GAIN 3.5500448048 (3.4)
H1:SUS-ETMY_L2_DRIVEALIGN_Y2L_GAIN 0.8850832254 (1.95)
H1:SUS-ETMY_L2_LOCK_P_GAIN 0.94 (0.96)
H1:SUS-ETMY_L2_LOCK_Y_GAIN 1.0 (1.01)
ETMX sus callines were disabled (because we haven't successfully get back to EX-only), and ETMY sus callines were enabled instead, and were accepted.
H1:SUS-ETMX_L1_CAL_LINE_CLKGAIN 0
H1:SUS-ETMX_L2_CAL_LINE_CLKGAIN 0
H1:SUS-ETMY_L1_CAL_LINE_CLKGAIN 150
H1:SUS-ETMY_L2_CAL_LINE_CLKGAIN 400
This morning I attempted to measure some transfer functions of the TTFSS out by the PSL rack. In short, it
didn't work. Enabling the TEST2 input did not do anything. The switch can be enabled inside the enclosure
however. I also took some noise measurements of the fast and EOM when the fast gain was varied between
9 dB and 19 dB.
Unfortunately I cannot retrieve the data from the floppy disc because either my floppy drive does not
work (unlikely) or I did not pay attention as to what format the HP4395A formatted the disc to (LIF as
opposed to DOS).
Fixing the TTFSS field box will require some laser down time, or more correctly, some FSS down time.
- There is an unsolved problem somewhere around DARM_TO_RF. I believe it has to do with the DIFF PLL OFFSET stepper servo not quite working fast enough to keep H1:ASC-AS_A_RF45_Q_SUM_NORM near enough to 0 before the switch happens. I am able to slowly step through the state successfully, but not request beyond it with the guardian without losing lock. - I removed REDUCE_RF9_MODULATION_DEPTH from the guardian path because this seemed to trigger the 1.4 Hz DHARD instability. I have been able to sit at NLN for 6 hours without problems. - We are still controlling DARM with L1 and L2 on ETMY and L3 on ETMX. Because of this the calibration is a complete mess at low frequency. At high frequency it is good to one percent (assuming we trust the PCAL at this point, unclear if we do because the force coefficients are changing.) I fiddled with the DARM calibration screens and switched the calibration back to ETMY L1 L2 such that the DARM calibration should be good to 15% according to PCAL. Some notes about the noise with the actuator switch: - MICH FF would need retuning, since MICH is coherent with DARM. - The ISS coupling to DARM was reduced at high frequencies. However, after two hours of sitting locked at NLN, the ISS is back to limiting high frequency DARM. - The scatter shelf is back and happens pretty consistently every two minutes. I did a couple of ISS broadband injections and TFs to test the arm power and intensity noise. I attached the TF template. Some notes: - Our ambient input RIN is ~10-8, according to ISS OUTER RIN. - DARM is limited by the ISS at high frequency (~2k on). DARM is not limited by the ISS anywhere else. - Arm RIN/Input RIN goes like f-1 as expected. - DARM/Input RIN goes like f-5 according to my TF measurement, and not like f-3. I do not yet understand this, I would have predicted -3, with -1 from the CARM pole filtering of the Input RIN, and -2 from the compliance of the quads coupling due to radiation pressure effects. - DARM/Arm RIN goes like f-4. - All the DARM/Arm RIN TFs seem to be nearly the same magnitude. Some fits must be applied to be able to really tell. - To calibrate I used the DARM FOM calibration for DARM meters, and found the average value of the Arm QPDs and divided by them. I assumed that ISS OUTER RIN was already calibrated. While doing some of these injections I excited ETMX mode 9. I ran ENGAGE_ALL_DAMPING in the violin mode guardian, this worked.
I've found the error in the above results. The DARM calibration stored in the DTT templates was incorrect, or at least very different from Keita's stopgap calibration from January 2019. Using Keita's DARM calibration I got sensible results, i.e. DARM/Input RIN goes like f-3, and DARM/Arm RIN goes like f-2. Attachment one shows DARM/Input RIN. The results agree pretty well with Gabriele's simulation, within a factor of two (At 30 Hz, my measurement gives 1.1e-12 m/RIN while Gabriele predicts around 7e-13 m/RIN) I am not sure how Gabriele has defined DARM, I have used Keita's stopgap which assumes DARM = Lx-Ly. If we trust the equation from alog 46759, and my by-eye fits here of Arm RIN/Input RIN and DARM/Input RIN, we can calculate the differential arm power: Δ Parm = 2 π2 m c α / β = 11.9 kW where α is the DARM/Input RIN f-3 fit coefficient = 3e-8 m/RIN, and β is the Arm RIN/Input RIN f-1 fit coefficient = 5.9e-1 RIN/RIN. If we assume that my arm power calculations were correct of 143.0 kW of average arm power, and that the 8% difference is real, we would get 143.0*0.08 = 11.4 kW
today it is snowing, and we have been having ALS glitches in the X arm for the last 45 minutes or so.
We wrote a quick script to transition the green lock to the configuration where the fiber is bypassed, and switched back and forth a few times. The attached text file can just be copied and pasted into a guardian shell, to either transition to the bypassed configuration or back to the normal configuration, you will also need to change the guardain request as the text file tells you to.
In the attached screenshot you can see that when IN1EN is 1, we are locked with the laser to the PLL , and there is some fuzz on the X arm transmission which is a series of small fast glitches if the plot were more zoomed in. When IN2EN is 1 we are locked directly to the arm, and in the first couple of examples this does seem to be quieter than with the laser locked to the fiber. There was a time labeled error when we accidentally left both feedback paths on, we can ignore this.
The arm comes unlocked fairly often when we are locked with the fiber bypassed. Next time this happens and we have time to work on this we should go the end station and take some time to measure the transfer function of this lock to the arm.
We have had other difficulties locking today, with the CARM offset reduction.
Last sunday, after the computer crash we had moved the VCO compensation filter in the TR CARM loop which used to be engaged when we transitioned to TR_CARM to later in the locking sequence, and we never understood why that was necessary. Today we moved it back to earlier in the sequence and that has improved the stability of the TR CARM loop. We also have been sometimes manually deceasing the gain in this path a bit to give us more stability through the CARM offset reduction. We tried to put this into the guardian once, but that didn't work so we have removed it again.
In preparation for adding the second HV driver to the OMC PZT driver chassis, the OMC model was updated.
Model has been restarted with new channels.
On January 8th I tried to measure the average arm power by dithering SRCL. Last night I did it again, this time with better TFs taken simultaneously. Average Arm Power = 143.0 +- 5.8 kW This time I directly fit each of the four Arm Trans QPD RINs (H1:ASC-{X,Y}_TR_{A,B}_NSUM_OUT_DQ) to DARM (H1:CAL-DELTAL_EXTERNAL_DQ), then fit a 1/f2 (attachment one). The DARM calibration used was the stop gap made by Keita. The average powers for the RIN calculation are as follows, and are good to +- 300 cts:Arm Trans QPD counts XA 145658 XB 191409 YA 207723 YB 221769This time the math is simpler:P_arm = DARM/ArmTransRIN Fit × π2 × m × cIf we look at the different in the arm trans RIN response between the arms, and say that the RIN we see is entirely due to radiation pressure in the arms, we get(DARM/Y)/(DARM/X) =,X/Y= 1.08meaning there may be 8% more light in the X arm than the Y arm. EDIT: It is actually the Y arm with 8% more light than the X arm. If we calculate the simple power recycling coupled cavity, I find that the estimated average ETM scatter losses are around 92 ppm and the estimated PRG here is 39. (attachment three) The measured value of PRG at the time of the measurement is 41.8, and the true input power was 26.5 W (requested was 30W). If we take these numbers to be true, then our arm gain according to the SRCL dither is 258.
Some simulation work related to this measurement.
From galaxy, I find that LHO's ITMX (ITM07) has a reflectivity of R_ITMX = 1.50%, while LHO's ITMY (ITM11) has a reflectivity of 1.42%. So there's quite an imbalance there.
I set up a simple simulation, using only the TEM00 mode, so without including any mismatch. Each arm has about 92 ppm of total round trip losses, following Craig's estimate. The first plot below shows some powers as a function of the two ITM reflectivities.
The red dot represent the nominal condition, which gives, for 1 W input power
PRG = 42.3
REFL = 17 mW (carrier only, TEM00, perfect matching)
AS = 0.9 mW (carrier only, TEM00m, perfect matching, nominal DARM offset of 1.2e-11 m
XARM = 5536 W
YARM = 5848 W
X/Y = 0.946 [more power in Y arm than X arm]
So there is more power in the Y arm than in the X arm, as one would expect since ITMY has higher reflectivity, so that the Y arm has higher finesse.
I also tried to reproduce more closely Craig's SRCL dither measurement. So in simulation, I computed the transfer function from SRCL motion to the RIN as measured in transmission of both arms. The plot below shows the simulated transfer functions RIN_ARM / SRCL for X and Y:
The numerical values are
RIN_X / SRCL_z = 1.088e6 /m
RIN_Y / SRCL_z = 1.034e6 /m
so (RIN_X / SRCL_z ) / (RIN_Y / SRCL_z) = 1.052. This is the ratio of powers, since the simulated transfer functions from SRCL to powers are equal for both X and Y, so the transfer functions to RIN are scaled by the inverse of the power.
Craig's measurement is actually the transfer function DARM / RIN while injecting on SRCL. In simulation, I used the AS port power as a proxy for DARM and computed the transfer functions TF(AS_DC / SRCL) and TF(RIN / SRCL). Then the equivalent of Craig's DARM / X and DARM / Y should be, at 30 Hz,
TF(AS_DC / SRCL) / TF(RIN_X / SRCL) = 98.4 W
TF(AS_DC / SRCL) / TF(RIN_Y / SRCL) = 103.6 W
and the frequency dependency is shown in the plot below (1/f^2 as expected).
So the equivalent of Craig's ratio (DARM / Y) / (DARM / X) should be
[ TF(AS_DC / SRCL) / TF(RIN_Y / SRCL) ] / [ TF(AS_DC / SRCL) / TF(RIN_X / SRCL) ] = 103.6 / 98.4 = 1.053
which is greater than one as in Craig's measurement, but corresponds to the ratio POWER_Y / POWER_X.
So the conclusion from my simulation is that the ITM different reflectivities gives a ratio of TF (as measured by Craig) greater than 1, which corresponds to higher power in the Y arm than in the X arm (the opposite of what Craig's concluded...)
I didn't know that the ITMs were not the same reflectivity. This is absolutely mind-blowing information. I reported higher arm power in the Y arm before, from the HEPI measurement. The RIN/SRCL TF corresponds to Equation 12 here. It is not dependent on the arm power at all, but rather the optical response γ of each arm to the SRCL dither. Also, the DARM/RIN TF in Equations 20 and 21 also indicate that DARM/RIN = 4*Parm/(m c ω2), so I made a mistake last night.
Good that the measurement and the prediction agree that there is more power in Y than in X.
Now we have to figure out why the measurement gives 8% imbalance while from the ITM reflectivities we only get 5%.
Updated simulation:
No change in the conclusions. Same imbalance of the arm powers as before (about 5%)
Adding the substrate lenses do not change significantly the power imbalance.
ITMX: static lens -310km, thermal lens +770km
ITMY: static lens +570kn, thermal lens +350km
Follow up to the discussion at today's commissioning call.
I computed the transfer function from laser relative intensity noise at the IFO input (called rin below) to DARM (calibrated in meters).
The input power is 26 W, and the round trip losses are adjusted to get a recycling gain of about 42. In the blue trace below, the two ITMs have the same reflectivity, equal to the nominal value of 1.4%. In the orange trace the two ITMs have different reflectivities, ITMX = 1.50% and ITMY = 1.42%, from the measured values from galaxy. This is the same configuration used in the other simulations, that gives a 5% power imbalance.
The dashed green curve is a simple radiation pressure model according to the equation below:

where RIN_arm / RIN_input is basically the double cavity pole (since input RIN is filtered by this transfer function. I used the simulated result), Delta P is the DC power difference in the arms ( Y - X = 7.7 kW) and m is the mirror mass. This matches quite well the low frequency simulation.
Using the simulated transfer function I can see what level of RIN at the IFO input would limit the sensitivity. It turns out that one needs a RIN of about 5e-6 (W/W)/rHz.
I found a mistake in my previous RIN simulation (many thanks to Matt Evans for spotting the inconsistency). Here's the correct results and plots.
Follow up to the discussion at today's commissioning call.
I computed the transfer function from laser relative intensity noise at the IFO input (called rin below) to DARM (calibrated in meters).
The input power is 26 W, and the round trip losses are adjusted to get a recycling gain of about 42. In the blue trace below, the two ITMs have the same reflectivity, equal to the nominal value of 1.4%. In the orange trace the two ITMs have different reflectivities, ITMX = 1.50% and ITMY = 1.42%, from the measured values from galaxy. This is the same configuration used in the other simulations, that gives a 5% power imbalance.
The dashed green curve is a simple radiation pressure model according to the equation below:

where RIN_arm / RIN_input is basically the double cavity pole 0.6Hz/fr (since input RIN is filtered by this transfer function), Delta P is the DC power difference in the arms ( Y - X = 7.7 kW) and m is the mirror mass. This matches quite well the low frequency simulation.
Using the simulated transfer function I can see what level of RIN at the IFO input would limit the sensitivity. It turns out that one needs a RIN of about 2e-7 (W/W)/rHz.
Doesn't this 2e-7 /rtHz RIN seem dangerously close to the measured value at 30Hz?
The intensity noise projection in the noise budget is made by injecting into the ISS second loop. It shows that the intensity noise is not close to DARM. 45828
Per Q1800019, I visually inspected H-GV12 on Dec. 19 to verify that the spindle nut and lock washer are present. Was not able to inspect torque setting without fall protection.
I forgot to add that the USGS java client needs to be running on the seismon machine as well. This lives in /usr/local/seismon/ProductClient, there is a script called init.sh. This is launched with the command:
controls@seismon:ProductClient 0$ ./init.sh start
However, the client often gets confused or something by old data in the /usr/local/seismon/ProductClient/data folder, it's probably best to remove this folder:
controls@seismon:ProductClient 0$ rm -rf data/
When the client starts, it will populate this folder and subfolders. I think it works okay to remove this folder while the client is running, but if that doesn't work the USGS client can be stopped with:
controls@seismon:ProductClient 0$ ./init.sh stop