In the past week I have powered up an IFR 2023A signal generator which has been in the C4 remote rack.
This one will be temporarily used as a 9 MHz RF seed source for the interferometer sensing and control (ISC) until we get a cool crystal oscillator.
SInce the 2023A needed an AC power, I laid down a long yellow power cord from wall to the C4 rack. Although this cord will be gone in some future, please be aware of it.
- - Current settings:
Carrier freq = 9099471 Hz
RF level = 10 dBm
Modulations = OFF
no SYNC
Keita and Vincent had reported some time ago that the BIO_STATE_REQ (the EPICs channel in which one requests to change the state of the analog filtering in the coil drivers) was not switching the digital filters in the COILOUTF bank like it's supposed to. This cropped up after the big upgrade back in late October. Turns out it was just two tags that were swapped -- the CTRL bit word and the MASK bitword, which are sent to the cdsCtrlFilt had been switched. My bad. I fixed this bug in ${userapps}/sus/common/models/TMTS_MASTER.mdl, committed, recompiled, re-installed, restarted, and restored the TMTS, and have confirmed the the digital filters switch according to the BIO_STATE_REQ as designed. ------------------- In doing so, I made sure that H1 SUS TMSY's safe.snap was up-to-date, and followed the current schema. The safe.snap now lives here: /opt/rtcds/userapps/release/sus/h1/burtfiles/tmsy/h1sustmsy_safe.snap (which had lived in ETMY's folder, for some reason, prior to my update). It's not properly soft-linked in the target directory as /opt/rtcds/lho/h1/target/h1sustmsy/h1sustmsyepics/burt/safe.snap Regrettably, I'd restarted the front-end before remembering that the TMS watchdog was hooked up to the BSC6-ISI. So, upon restart, the BSC6-ISI, who had been running with some if his stage 1 isolation loops, watchdog tripped which -- going from isolated to tripped -- sent a "jolt" big enough to trip the very-sensitive QUAD watchdog. No one was "hurt," but it meant I had more restoring to do than initially intended. I've restored the TMS, ETMY to be fully damped and functional. Because the user scripts for the ISI are still pretty user-unfriendly (IMHO), and I think Vincent had BSC6-ISI in some "non-standard" configuration, I didn't wanna "risk" bringing the isolation loops back up, so I've left the ISI with damping loops for both stages on (only). [[Everything in quotes are stronger words than what happened. That's why I put them in quotes.]]
The ITMy blade ECD magnet have been removed in preparation for the upcoming magnet coupling measurements by Robert Schofield. Also, while in chamber, I added PEEK tabs to both ITM and CP First Contact to facilitate removal before closing the chamber. I will resume work on suspending and alignment when a final decision has been made with respect to ISI table level.
I have filled out H1 SUS ETMY's new infrastructure, including (1) Filling in the ISI to SUS WIT and SUS to ISI OFFLOAD paths, installed as was described for H1 SUS PR2 in LHO aLOG 4553. Nothing new -- same exact filters -- just using the H2 SUS ETMY (yes, H2 -- the SUS hasn't moved yet) matrices from /opt/rtcds/userapps/release/isc/common/projections/ISI2SUS_projection_file.mat (2) Installing the OPTICALIGN alignment offset calibration gain, as described in LHO aLOG 4563. Here, for this and all QUADs, the gain is OPTICALIGN GAIN [cts/urad] = ( DAC [V/ct] * Coil Driver [A/V] * Coil/Magnet [N/A] * HSTS M1 to M3 [rad/N.m] * 1e9 [nrad/rad] )^-1 = ( (20/2^18) * 0.009943 * 1.694 * 0.033514 (for Pitch) * 1e9 )^-1 = 0.023219 [cts/nrad] for Pitch = ( (20/2^18) * 0.009943 * 1.694 * 0.015055 (for Pitch) * 1e9 )^-1 = 0.051689 [cts/nrad] for Yaw Note that I've gone with nanoradians instead of microradians (as was done for PR2), because the alignment offsets needed to align (at least the H2OAT) were already quite large (~75% of the M0 BOSEM range), so calibrating this gain into microradians (or any gain larger than 1, really) would have saturated the DAC. This provides for annoying large EPICS values, (retaining the -3027 and +5405 [ct] offsets needed for the H2OAT, means that these offsets are 58562 and 232783 [nrad]), but I think we can deal. I still need to adjust the OPTICALIGN screen to account for this difference (make the sliders have bigger default range and step size, as well as changing the legend to match). (3) With further quantitative assessment pending, I've installed Rana's 2k to 16k anti-imaging filter in the L3_ISCINF_P L3_ISCINF_Y filter banks, in order to filter any imaging noise that arises from the inter-process-communication between the ASC model (running at 2k) and the SUS model (running at 16k). I attach a bode plot of the filter as installed (again, identical to Rana's).
As of this entry, I've updated and committed H1 SUS ETMY's safe.snap here,
${userapps}/sus/h1/burtfiles/etmy/h1susetmy_safe.snap
as well as saved and committed the updated foton filter here,
${userapps}/sus/h1/filterfiles/H1SUSETMY.txt.
For both, I've checked that they're obeying the new schema, in which
/opt/rtcds/lho/h1/target/h1susetmy/h1susetmyepics/burt/safe.snap
and
/opt/rtcds/lho/h1/chans/H1SUSETMY.txt
are soft links to the above userapps locations.
S. Aston, J. Kissel
Stuart was double checking my work (hooray!) and found several problems with my implementations of the OPTICALIGN offsets and gains.
(1) There's a typo in the labelling of the calculation (I wrote "for Pitch" twice, when one should be Yaw). The corrected statement is
"For this and all QUADs, the gain is
OPTICALIGN GAIN [cts/urad] = ( DAC [V/ct] * Coil Driver [A/V] * Coil/Magnet [N/A] * HSTS M1 to M3 [rad/N.m] * 1e9 [nrad/rad] )^-1
= ( (20/2^18) * 0.009943 * 1.694 * 0.033514 (for Pitch) * 1e9 )^-1
= 0.023219 [cts/nrad] for Pitch
= ( (20/2^18) * 0.009943 * 1.694 * 0.015055 (for Yaw) * 1e9 )^-1
= 0.051689 [cts/nrad] for Yaw
(2) In my haste, I'd installed these gains exactly backwards (0.023 for YAW and 0.052 for Pitch). In fact, even further, I had calculated the offsets to-be-restored with the gains exactly flipped as well. Whoops! I've now corrected the gains, and changed the stored offsets to
Pitch: -3027 [ct] / 0.023219 [cts/nrad] => -132302 [nrad]
Yaw: +5405 [ct] / 0.051689 [cts/nrad] => 104548 [nrad]
I'm Currently taking measurements, but I'll take a new safe.snap once I'm finished.
New safe.snap has been captured and committed to the userapps repo, as of version 3401: /opt/rtcds/userapps/release/sus/h1/burtfiles/etmy/h1susetmy_safe.snap
We had a kernel crash of the internal cds servers cdsldap0 and cdslog this weekend. Both computers are in the H2EE room, but only these two crashed.
The loss of cdsldap0 meant that remote 2FA log into CDS was not working. Neither was using your ligo.org account on the internal CDS workstations.
I restarted the servers and all looks good so far. Both machines had been running for 342days, so they needed file system checks.
Check ResourceSpace for the photo collection of last week's cartridge move. This is the one-arm test cartridge that came out of BSC 8 early in October 2012. Once on the test stand in October, the ISI's folding mirror suspension was transferred to the neighboring BSC 2 ISI and re-christened as the beam splitter suspension while the quad's position was adjusted on the BSC 1 ISI. SUS locking photos courtesy of Jeff Bartlett.
Gathering closed loop transfer functions on H1 SUSITMY, started ~1:30p ET / 10:30a PT, will cease (regardless) at 3:00p ET / 12:00p PT.
Transfer functions complete.
[Dick / Kiwamu]
We found an RF cable whose signal level depends on the angle of one of the cable end. This is not good. I consulted with Filiberto on this issue and we decided to leave it to the electricians who are coming in the next week from Caltech. Or if the cable turns out to be necessary soon, we can just swap or fix it by ourselves.
--- the Cable
place: remote rack C4
connection between : U42-1 and U9-1
description:71 MHz for a VCO
length: ~ 2 m
type: N male / N male
--- Symptoms
* The RF power dropped from 11 dBm to -8 dBm suddenly while doing nothing
* Applying tension at the cable end (the U9-1 side) introduces variation in the RF power by ~15 db or so.
--- Assessment
At the beginning we thought that the power variation was due to the connector which is a part of the U9 circuit box (i.e. the channel 1 output of an RF distribution amplifier D100024/S1000595). We pulled out the circuit box and brought it to the EE shop to do a further investigation. We didn't find anything wrong. So we put the box back to the rack and it seems working fine.
Eventually we located the issue and confirmed that it was in the RF cable and not in the box. Currently everything is back to place.
I have just removed the cable and cut it so that noboday can accidentally use it.
For the 35W beam
The 59 Hz chiller pumps at EY produce turbulence in the water lines that results in a peak at about 9 Hz in seismic spectra at Y-end. This peak creates problems e.g. for ISI. We have been planning to install a variable frequency drive (VFD) at EY so that we could reduce the water flow, in hopes of reducing the turbulence. The VFD was installed at EY this week and I ran some tests at various frequencies (pump speeds). Figure 1 shows that the peak is nearly at background with the VFD set to 30 Hz, instead of the nominal 60 Hz. 40 Hz is also pretty good so we decided to run at 35 Hz from now on. We believe that the cold water flow rate is down by less than a factor of 2 and that this should be sufficient for our needs. We will find out for sure when it gets hot next summer. We also now have VFD at EX and the corner station so we can adjust these as needed.
End Y is, as of now, in a seismic condition pretty similar to what we plan for aLIGO science mode. There are still a few pumps making sharp lines, but the broad band should be pretty close, especially when people are not out at End Y. To test the pointing of the seismic array, I placed a shaker on the floor at two locations Wed. night, running at 12 Hz. The times were:
Nov. 15 2012 0:54:54 UTC to 2:20:40 UTC (last ten minutes were the most quiet) and
Nov. 15 2012 2:29:40 UTC to 3:00:00 UTC (first fifteen minutes were the most quiet).
Robert S., Richard M., John W.
Attached are plots of dust counts > .3 microns and > .5 microns in particles per cubic foot from approximately 6 PM Nov. 15 to 6 PM Nov. 16. Also attached are plots of the modes to show when they were running/acquiring data. There is still an occasional calibrate failure alarm on the dust monitor in the OSB optics lab. Dust monitor 4 in the LVEA was turned back on.
[Michael Rodruck, Alberto]
Today we finished setting up the optical path to couple the PSL reference cavity tranmsitted beam into the ALS fiber. After we mode matched the beam to the fiber launcher, we aligned it into the fiber by using the OzOptics auxiliary fiber laser. We coupled 3.0mW into the fiber, out of the 5mW coming from the reference cavity: a 60% matching. It didn't look like this could be imrpoved by much.
Both ALS setups on the PSL table are now almost complete. The only work left to complete is the replacement of the Faraday's mount on the ISCT1 pick-off path: the mount is currently under construction at the machien shop.
Details on the optical alyotu of the fiber setup are in LIGO-T1200471-v7.
One hypothesis for the source of excess vibration noise on the PSL table from the crystal chiller circuit (here) is that the ~2 mm aperture in the quick-connect hose fittings on the 5/8” ID hoses causes a turbulent jet of water that, especially if bubbles are present, modulates the flow of water. Figure 1, lower plot, shows that a quick-connect is about two orders of magnitude more noisy than a barbed barrel connector for the 10 - 15 l/m flow through the crystal circuit of the crystal chiller. Figure 2 has a photograph of the setup.
To see if the noise from the quick connect might be loud enough to explain the noise from the whole circuit, we clamped the quick connect setup used for the above measurement to the outside manifold of the crystal box (setup photo shown in Figure 2). The upper plot in Figure 1 compares the nominal noise to the noise from this setup. The peaks produced in this way are relatively large but don’t match the peak from nominal flow through the box. However, the momentum transfer to the table for our test is much different than in the actual setup.
I think the results are suggestive enough that it would be worth an experiment where we replace the two quick connects at the crystal box manifold with barbed connectors. To further improve the flow, we suggest that we use the capped threaded holes for this in order to make one less 90 degree turn. Figure 2 also has a photograph illustrating the proposed modification.
Robert S., Michael R., Rick S.
WP#3568
Following the wiring of the new BSC6 75l/s Ion Pump, I created a new database file for the h0veey VME IOC called HVE-EY:75IPBSC6.db. This is essentially a copy of the existing BSC10 database, with BSC10 replaced by BSC6 and 411 replace with 425.
At 13:31 we restarted h0veey with the new database, all went well. I also changed:
I also fixed the MEDM to MEDM links for the vacuum screens on the control room machines.
Unifirst arrived with floor mats. A viewport was installed in the septum between HAM 1 and 2. Michael R. transitioned the LVEA to laser hazard for MC locking work. Michael R. transitioned the LVEA to laser safe. Richard and Dave added the ion pump on BSC6 to the control system. Michael R. and Alberto worked on aligning the PSL ALS optics. Dale lead a tour through the control room.
This afternoon Andres and I removed the H1-Pr3 and H1-PRM HAM suspensions from their storage containers and placed them on the chamber-side optics table in the LVEA. No problems were encountered during the move.