TITLE: 02/21 Day Shift: 16:00-00:00 UTC (08:00-16:00 PST), all times posted in UTC
STATE of H1: Planned Engineering
INCOMING OPERATOR: None
SHIFT SUMMARY:
Primary Ongoing Activities
Control Room Log (02/20) so far..
LOG:
| Start Time | System | Name | Location | Lazer_Haz | Task | Time End |
|---|---|---|---|---|---|---|
| 19:22 | SAF | LVEA is Laser HAZARD | LVEA | Yes | LVEA is Laser HAZARD | 03:59 |
| 16:23 | VAC | Gerardo, Jordan | LVEA | Yes | Vacuum Checkup | 16:40 |
| 16:46 | CDS | Fil, Ryan S | EX | N | CDS Work | 18:21 |
| 16:47 | CDS | Tony, Jonathan | EX | N | CDS Work | 18:21 |
| 16:53 | CDS | Erik | Control Rm | N | Dolphin Fencing EX | 17:13 |
| 17:01 | VAC | Jordan, Janos, Gerardo | FCES | N | HAM8 Vent | 20:18 |
| 17:07 | FAC | Karen | EY | N | Technical Cleaning | 17:55 |
| 17:07 | VAC | Kim | EX | N | Technical Cleaning | 17:45 |
| 17:29 | SQZ | Camilla, Vicky | FCES | N | Move SQZT8 Out of the way | 18:29 |
| 17:44 | FAC | Kim | FCES | N | Technical Cleaning | 18:44 |
| 17:45 | SQZ | Nutsinee, Naoki | LVEA | Yes | SQZT Work | 20:15 |
| 17:55 | EE | Marc, Fernando | CER Mezzanine | N | Looking for a temp gun | 18:00 |
| 18:00 | EE | Marc | H2 Building | N | Looking for a temp gun | 18:03 |
| 18:17 | FAC | Chris | FCES | N | Helping tech clean | 21:13 |
| 18:21 | CDS | Tony, Jonathan, Fil, Ryan S, Dave | MX, EX | N | CDS Work | 19:28 |
| 18:38 | SQZ | Daniel | LVEA | Yes | SQZ Work | 20:15 |
| 18:57 | EE | Marc | LVEA | Yes | Checking on activity | 19:17 |
| 19:23 | FARO | Ryan C | LVEA | Yes | Water level check | 19:34 |
| 19:29 | CDS | Tony., Jonathan, Ryan S, Dave | FCES | N | CDS Work | 20:37 |
| 19:48 | CC | RyanC | CER | N | Handheld DM checks | 19:51 |
| 20:21 | VAC | Janos | LVEA | Yes | Tool Pickup | 20:28 |
| 20:29 | SUS | Jim | EX | N | BRS Centering | 21:14 |
| 20:38 | CDS | Tony, Jonathan, Dave | EY, MY | N | CDS Work | 22:40 |
| 21:01 | EE | Marc, Jabari | MY | N | Parts | 22:00 |
| 21:07 | VAC | Jordan, Gerardo, Janos, Travis | FCES | N | HAM8 Vent | 22:19 |
| 22:08 | CDS | Ryan S, Fil | EY | N | CDS Work | 22:08 |
| 22:20 | EE | Fil | FCES | N | Cable Repair | 23:16 |
| 22:25 | VAC | Janos, Gerardo | LVEA | Yes | Tubopump/Vacuum Stuff | 00:04 |
| 22:42 | CDS | Tony, Jonathan, Dave | Mechanical Room | N | CDS Work | 23:42 |
| 23:12 | FARO | Ryan C | LVEA | Yes | Faro prep for tomorrow | 23:22 |
| 23:17 | EE | Fil | LVEA | Yes | Terminating Beckhoff network cables | 00:17 |
| 23:23 | TCS | Ibrahim | Mech Room | N | Check TCS chillers | 23:52 |
TCS Chiller Water Level Top-Off BiWeekly - Closes FAMIS 26168
Neither chiller was under its threshold min
TCS Y - Added ~300ml
TCS X - Added ~150ml
Leak Tub is dry
Closes Weekly FAMIS Task 25979
ETMX_ST1_CPSINF_V2 BSC High Freq noise is elevated.
FAMIS 20016
PMC reflected power has continued to increase while transmitted power has been decreasing.
LVEA is STILL in LASER HAZARD
Primary Ongoing Activities
Control Room Log (02/20) so far..
WP11693 Vicky, Camilla, Chris.
In preparation for the for HAM8 +Y door removal, after HAM8 was been vented, we put guillotine in the viewport and removed the bellows between HAM8 and SQZT8. Bellows is wrapped in foil on top of SQZT8. We rolled SQZT8 enclosure out of the way of the door crew (it's position was already marked and parts on table secured 75831, 75829).
Tue Feb 20 08:10:02 2024 INFO: Fill completed in 9min 58secs
Jordan confired a good fill curbside. Note this fill ran at 8am today before the CDS network upgrade work commenced.
TITLE: 02/20 Day Shift: 16:00-00:00 UTC (08:00-16:00 PST), all times posted in UTC
STATE of H1: Planned Engineering
OUTGOING OPERATOR: None
CURRENT ENVIRONMENT:
SEI_ENV state: CALM
Wind: 5mph Gusts, 4mph 5min avg
Primary useism: 0.04 μm/s
Secondary useism: 0.37 μm/s
QUICK SUMMARY:
Control room workstations were updated and rebooted. Operating system packages and conda packages were updated.
In conda, ndscope was updated to 0.19.1, with numerous improvements.
Diaggui was updated to 4.0.4, which fixes a crash when loading certain xml files.
Daniel, Dave:
h1ecatc1, the Beckhoff slow controls system, crashed at 15:38 this afternoon. The EDC is showing 35365 disconnected channels. The computer is completely unresponsive, including its management port. It will need a manual reset.
The alarms system restarted itself at this time. The ongoing HAM6 alarms remain bypassed, and in addition I have bypassed some invalid temperatures channels
Bypass will expire:
Tue Feb 20 03:49:26 AM PST 2024
For channel(s):
H0:VAC-LX_Y0_PT110_MOD1_PRESS_TORR
H0:VAC-LY_Y1_PT120B_PRESS_TORR
H1:PEM-C_CER_RACK1_TEMPERATURE
H1:PEM-C_MSR_RACK1_TEMPERATURE
H1:PEM-C_MSR_RACK2_TEMPERATURE
H1:PEM-C_SUP_RACK1_TEMPERATURE
Updated to the most recent svn, and restarted.
WP11702
The file copy completed at 12:23 Sun 18th Feb. This morning I reconfigured NDS1 daqd to serve the past 6 months of data from the permanent archive area, daqd was restarted at 08:44 this morning.
The old files were then deleted from TW1's SSD-RAID between 08:53 and 10:54, taking 2hours 1min.
Mon Feb 19 10:11:56 2024 INFO: Fill completed in 11min 52secs
Start time has been changed to 08:00 for tomorrow's early fill prior to CDS network upgrades.
Sun Feb 18 10:10:41 2024 INFO: Fill completed in 10min 37secs
Sat Feb 17 10:10:46 2024 INFO: Fill completed in 10min 42secs
WP11702 TW1 offload
I've started the process of offloading the past 6 months of raw minute trends from TW1's SSD-RAID to h1ldasgw1's permanent storage.
The first step was to freeze the almost full directory and switch TW1 over to writing to a new empty area, and then temporarily configuring NDS1 to serve data from the frozen dir while the file copy is in progress.
To this end, NDS1 daqd was restarted at 10:14 PST this morning.
as of 13:23 copy is 9.3% complete, ETA 11:39 Sunday morning.
Today's activities: - HAM7 pumpdown status: ~3.3E-6 Torr - Corner pumpdown status: ~3.9E-1 Torr. On Tuesday, transitioning to Turbo (Y-manifold; OMC; HAM6) - EX pumpdown status: 3.75E-8 Torr: the post-vent RGA scan is ready, the results will be in the comment comment section, once they are published. The comparison with past RGAs is also coming next week. If the results will be considered satisfactory, the Ion-pump will be valved in. The GV will remain closed during FAC works - The purge air supply at FCES is switched on, in order to start HAM8 vent first thing next week
Naoki, Nutsinee, Daniel
We installed all the optics for PMC and locked the PMC with p-polarization. We will lock the PMC with s-polarization and align SHG, CLF, seed next week.
First we put a HWP before PMC and changed the beam to the p polarization since the p-pol has much lower finesse in PMC and it is easy to align. The HWP angle is 152 for p-pol and 108 for s-pol.
We aligned two steering mirrors before PMC. Fig. 1 and 2 show the PMC trans (blue) and refl (red) with PMC scan. The mode matching is 93% and the refl dip reaches 88% from the maximum.
We found that the label of the pick off mirror before PMC REFL PD says R=5% for s-pol, but it was actually R=90% for s-pol and R=70% for p-pol. The PMC REFL power is ~30mW and more than 20mW was injected to PMC REFL PD, which is a lot. So we replaced this mirror with the mirror which is R=8% for s-pol and R=1% for p-pol.
Then we adjusted the demod phase of PMC PDH signal and locked the PMC with p-pol. The UGF is 1.3 kHz and phase margin is 67 deg as shown in Fig. 3. We accepted the SDF related to PMC as shown in Fig. 4.
Note that we will have 20 times more optical gain with s-pol because of higher finesse. Also we will have 8 times more power at PMC REFL PD with s-pol because of the pick off mirror. So we need to reduce the gain by 160 with s-pol to have the same UGF as p-pol.
After the pick-off mirror swap with 34mW input we have ~2mW hitting the PMC Refl. DC readout reads 75mW. The HWP before the PMC is set to s-pol at the moment.
Attached an updated picture of the SQZT0 table. All the optics are in.
The PMC PZT trigger has the PMC TRANS PD wired to channel 1 and PMC REFL to channel 2.
The DC readback of PMC_REFL is saturating and the gain adjust is broken due to a missing ground wire in the controls of aux concentrator 11 (which pegs the adjustable gain to 40dB).
Nevertheless, we were able to engage the guaduan to lock the PMC using the dip in reflection.