h1ecatx1, possible communication errors
Found reports of CRC errors on the following terminals on h1ecatx1:

End Link R4_5 (EL6692)
End Link L3_4 (EK1521)
ISC Common L0 (EK1501)

They are indicated by circles on the topology as shown in the first screenshot.

There were also lost frames and Tx/Rx errors as shown in the second screenshot.

I am not entirely clear on what this is a symptom of. Hitting 'Clear CRC' and 'Clear Frames' reset all of the above.
Images attached to this report
Comments related to this report
patrick.thomas@LIGO.ORG - 14:30, Wednesday 05 September 2018 (43839)
Plots of lost frames for all devices on h1ecatc1, h1ecatx1, and h1ecaty1 for the last 180 days. Something seems to have gone amiss with h1ecatx1 around August 7 2018.
Non-image files attached to this comment
patrick.thomas@LIGO.ORG - 14:37, Wednesday 05 September 2018 (43840)
Changes were made to the hardware that day: alog 43317.
patrick.thomas@LIGO.ORG - 14:40, Wednesday 05 September 2018 (43842)
The errors have returned at the same terminals.
patrick.thomas@LIGO.ORG - 15:04, Wednesday 05 September 2018 (43843)
The netid changed on July 11.